Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/29/2007 | FRAMING | Approved | IVRS - Inspection :* | |
| 01/25/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ADD STUD AT BOWED STUD GARAGE 2) NO DWV WATER TEST 3) WATER HEATER B-VENT MUST HAVE MINIMUM 30 PITCH |
|
| 01/18/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) BACKING UNDER FLOOR TOP STAIRS 2) H/D AND STUDS UNDER STAIRS 3) TIGHTEN REDHEADS 4) ADD R/H SOUTH WALL GARAGE 5) ADD STUD NEXT TO BENT STUD SOUTH WALL GARAGE 6) H2.5'S BOTH SIDES GLUE LAM 7) NEED HIP HANGERS GARAGE TRUSSES 8) WHY SECOND WALL AT WATER HEATER ? 9) BLOCK REGISTER IN DOOR 10) S/R NAILER ENTRY LID 11) ADD BLOCK BEHIND BEAM HANGER AT STAIRS 12) NO DWV WATER TEST 13) NAIL STOP 2" HALL FURR DOWN 14) NO SUPPLY TEST 15) NEED MORE PITCH WATER HEATER B-VENT 16) SECONDARY A/C DRAIN TO OBVIOUS LOCATION |