Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM03459
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/04/2007 | FRAMING | Approved | IVRS - Inspection :* | |
01/04/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) TRUSS REPAIR A02, B02 DAMAGED GUSSET, MISSING GUSSET |
|
12/13/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MISSING SIMPSON LTT-20B SHEARWALL STAIRWAY 2) FIRESTOP CHASE MASTER BATHROOM 3) MISSING LOAD WINDOW 4) LEAK AT LAV VENT BETWEEN 1ST & 2ND FLOOR ABOVE COMBUSTION AIR VENTS 5) SECURE VENT LINE AT UPSTAIR BATH 6) B-VENT NEEDS TO BE EXTENDED 7) LAUNDRY ? EXHAUST VENT TORN 8) BLOCK MECHANICAL BOOT DUCT IN DEN 9) NEED LTHJ HANGERS 2ND FLOOR BEDROOM 10) BLOCK UPPER COMBUSTION AIR VENT |