Permit: T06CM03443

Parcel: 11515137B


Addresses:

660 W SAHUARO ST


Inspection Status: Approved

Inspection History: ENGINEERING - FINAL

Permit Number - T06CM03443

Inspection Description - ENGINEERING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/16/2008 ENGINEERING - FINAL Approved
04/09/2008 ENGINEERING - FINAL Partial Approval CLARIFICATION OF PUNCH-LIST ITEMS LISTED ON PREVIOUS INSPECTION.
02/21/2008 ENGINEERING - FINAL Partial Approval OK FOR TEMP C OF O ONLY, PERMANENT C OF O NOT TO BE GIVEN UNTIL ITEMS LISTED BELOW ARE ADDRESSED:

1) NEW ACCESS SIDEWALK CROSS SLOPE IS >2%; PER COT DEV STD. 2-08.5 (CROSS SLOPE ON ALL SIDEWALKS WILL NOT EXCEED 2%).
2) INSTALLED SCUPPERS DO NOT MATCH THE SIZE OF DOWNSPOUTS TO ALLOW FOR ROOF DRAINAGE. DOWNSPOUTS ARE 4" SQUARE AND SCUPPERS ARE 1" X 6".
PROVIDE A STATEMENT FROM THE ARCHETECH OF RECORD, STATING THAT THE CONSTRUCTED ROOF DRAINAGE, DOWNSPOUTS, AND SCUPPERS ARE ADEQUATE.
3) PER COT DEV STD 2-08.4; SIDEWALKS WITH IN A PROJECT MUST BE PHYSICALLY SEPARATED FROM ANY VEHICULAR TRAVEL LANE BY MEANS OF CURBING, GRADE SEPARATION, BARRIERS, OR OTHER MEANS.