Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03443
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
02/13/2008 | ELECTRIC - FINAL | Not ready for Inspection | 1. GROUND EC-2 DISCONNECT ENCLOSURE 2. UNIT HEATERS REQUIRE DISCONNECTING MEANS 3. NUMBER BREAKERS PANEL "H1" LETTER/TEST RESULTS RECEIVED 4. REPAIR SERVICE DOOR SO IT CAN PROPERLY CLOSE |
|
02/08/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. GFI TEST REPORT TO STATE THAT THE TEST WAS PERFORMED PER MANUFACTURES INSTRUCTIONS AND THE RESULTS OF TEST PASS OR FAIL 2. STILL NEED LETTER OF TORQUE 3. PROVIDE PHYSICAL PROTECTION FOR SERVICE (BOLLARDS, PARKING CURBS, ETC.) 4. PROVIDE LADDER FOR INSPECTION STILL NEED FULL FINAL INSPECTION |