Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/14/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 01/29/2008 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* 1) NEED TO POST BOND FOR POWER 2) NEED TO PERFORM GFI TEST ON MAIN 3) OK STEEL, GAS AND WATER BOND 4) GEC TO XFMR TO BE #4 5) BONDING JUMPER FROM XFMR TO PANEL TO BE #4 6) SYSTEM BONDING JUMPER IN XFMR TO BE #4 7) RECEIVED LETTER FOR CHANGE IN SERVICE CONDUCTOR SIZE 8) PROVIDE LETTER OF TORQUE FOR TERMINATIONS IN SWITCH GEAR |
|
| 01/25/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : There is no access to the site.| 920* 1. BUILDING LOCKED. NO ONE ON SITE. 2. RECALL WHEN READY. NEED TO POST BOND FOR POWER |