Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06CM03443
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/14/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
11/26/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* SERVICE SECONDARY DITCH INSPECTION NEED SEALED LETTER ON CHANGES TO SERVICE SECONDARY RACEWAYS & CONDUCTORS. PLANS CALL FOR THREE SETS OF #600 CU. ELECTRICAL CONTRACTOR HAS CHANGED TO 4 SETS OF #500 AL NEED TO INSTALL A WARNING RIBBON MINIMUM 12" ABOVE SERVICE RACEWAYS ENTIRE LENGTH WHEN YOU BACKFILL OK TO BACKFILL SUBJECT TO LETTER FROM ENGINEER OF RECORD. |