Permit: T06CM03432

Parcel: 141316300

Inspection Status: Approved

Inspection History: EXT METAL CLIPS/EXT SHEATHING

Permit Number - T06CM03432

Inspection Description - EXT METAL CLIPS/EXT SHEATHING

Inspection Status - Approved

Date Description Inspector Results Comments
08/16/2006 EXT METAL CLIPS/EXT SHEATHING Approved IVRS - Inspection :*
08/15/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED PLANS/PERMIT ON SITE
08/10/2006 EXT METAL CLIPS/EXT SHEATHING Partial Approval IVRS - Inspection :*
1) NEED 2 X 2 X 10 BEAM OR 4 X 10 AT PATIO SLIDER
2) NEED 16D AT BEAM HANGER REAR PORCH AHUS 410
08/04/2006 EXT METAL CLIPS/EXT SHEATHING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) STRAP BEAMS TO LOAD BEARING POSTS
2) NAILS MISSING IN RSP4'S
3) SHEAR WALL STRAP (PER 7/SD2) MUST EXTEND PAST FLOOR TO WALL ABOVE
4) LADDER BLOCKS AND KLEETS MISSING PER 2/SD2
5) LOWER SHEAR PANEL ON EAST WALL MUST BE MIN. 4' WIDE
6) A34 CLIP REQUIRED AT GABLE END BRACING
7) DBL 2 X 6 REQUIRED UNDER INTERIOR 2 X 8 BEAM IN GREAT ROOM
8) PAD REQUIRED UNDER GIRDER POST IN GARAGE
9) INSTALL HANGERS UNDER ENTRY JACKS
10) NAIL ALL SLOPING LEDGERS PER PLAN
11) GABLE END BRACING MISSING AT ENTRY
12) PAD OVER LOAD BEARING HDR IN GREAT ROOM
13) STOPPED INSPECTION