Inspection History: PLUMBING - FINAL
Permit Number - T06CM03428
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/22/2007 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
01/17/2007 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* WATER HEATER TEMPERATURE & PRESSURE RELIEF SHALL BE APPROVED RIDGID PIPING FULL SIZE (NO FLEX) GRAVITY DRAIN TO DAYLIGHT PER 1/9/07 INSPECTION. SEAL INSULATION WITH CORRECT ADHESIVE |
|
01/09/2007 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* CLOSET FLANGES OK 1. SHALL INSTALL WATER HEATER PER DETAIL 204 ON P2.0 WATER HEATER TO SIT ON FLOOR, EXPANSION TANK TO BE SUPPORTED & SECURED, TEMPERATURE & PRESSURE RELIEF TO GRAVITY DRAIN TO DAYLIGHT 8' IN AND OUT OF WATER HEATER PIPING TO BE INSULATED. |
|
08/29/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* WATER TESTING NORTH (2) SETS RD + OFRD OK 1. SHALL SUPPORT ALL PIPING CORRECTLY + RECALL FOR INSPECTION. |
|
08/28/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 4" RP + 4" OFRD (2) SETS ON SOUTH SIDE OF BUILDING WATER TEST OK 1. NEED TO SEE TEST ON NORTH (2) SETS WITH SECURING OF PIPES + SEAL OF PIPE PENETRATIONS THRU BUILDING. |
|
08/02/2006 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* PLAN ONLY HAS DEMO OF GAS PIPING WHICH IS OK IT APPEARS BUILDING RAIN DRAINAGE SYSTEM FROM ROOF IS NEW, IT IS A SINGLE PIPE SYSTEM WITH RAIN DRAIN & OVERFLOW DRAINS TIED INTO SAME PIPE SYSTEM, PIPING IS NOT PROPERLY SUPPORTED THIS SYSTEM DOES NOT MEET CURRENT 2003 UPC OR LOCAL AMENDMENTS FOR RAIN DRAINAGE. |