Permit: T06CM03428

Parcel: 12407040B


Addresses:

745 E 9TH ST


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM03428

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
01/22/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
01/17/2007 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
WATER HEATER TEMPERATURE & PRESSURE RELIEF SHALL BE APPROVED RIDGID PIPING FULL SIZE (NO FLEX) GRAVITY DRAIN TO DAYLIGHT PER 1/9/07 INSPECTION. SEAL INSULATION WITH CORRECT ADHESIVE
01/09/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CLOSET FLANGES OK
1. SHALL INSTALL WATER HEATER PER DETAIL 204 ON P2.0
WATER HEATER TO SIT ON FLOOR, EXPANSION TANK TO BE SUPPORTED & SECURED, TEMPERATURE & PRESSURE RELIEF TO GRAVITY DRAIN TO DAYLIGHT 8' IN AND OUT OF WATER HEATER PIPING TO BE INSULATED.
08/29/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
WATER TESTING NORTH (2) SETS RD + OFRD OK
1. SHALL SUPPORT ALL PIPING CORRECTLY + RECALL FOR INSPECTION.
08/28/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
4" RP + 4" OFRD (2) SETS ON SOUTH SIDE OF BUILDING WATER TEST OK
1. NEED TO SEE TEST ON NORTH (2) SETS WITH SECURING OF PIPES + SEAL OF PIPE PENETRATIONS THRU BUILDING.
08/02/2006 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
PLAN ONLY HAS DEMO OF GAS PIPING WHICH IS OK
IT APPEARS BUILDING RAIN DRAINAGE SYSTEM FROM ROOF IS NEW, IT IS A SINGLE PIPE SYSTEM WITH RAIN DRAIN & OVERFLOW DRAINS TIED INTO SAME PIPE SYSTEM,
PIPING IS NOT PROPERLY SUPPORTED
THIS SYSTEM DOES NOT MEET CURRENT 2003 UPC OR LOCAL AMENDMENTS FOR RAIN DRAINAGE.