Permit: T06CM03428

Parcel: 12407040B


Addresses:

745 E 9TH ST


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03428

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/09/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/02/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. PLEASE REVISE PLANS FOR ADDED LIGHTING AT OFFICE AND BATHROOMS. ALSO FOR POWER CIRCUITS FOR LIGHTING DISPLAY AND MICROWAVE.
2. FILL UNUSED OPENING IN JUNCTION BOX, NOT OPEN FITTING
3. EMERGENCY LIGHTING TO BE ON CIRCUIT FOR AREA BEING SERVED BATHROOMS, OFFICE & BREAKROOM (700.12)
4. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8
5. USE APPROVED FITTINGS WITH CONDULETS -- NOT CHASE NIPPLE.
6. PLEASE PROVIDE ARC FLASH WARNING LABELING FOR PANELS.