Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03428
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/09/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/02/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. PLEASE REVISE PLANS FOR ADDED LIGHTING AT OFFICE AND BATHROOMS. ALSO FOR POWER CIRCUITS FOR LIGHTING DISPLAY AND MICROWAVE. 2. FILL UNUSED OPENING IN JUNCTION BOX, NOT OPEN FITTING 3. EMERGENCY LIGHTING TO BE ON CIRCUIT FOR AREA BEING SERVED BATHROOMS, OFFICE & BREAKROOM (700.12) 4. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO 406.8 5. USE APPROVED FITTINGS WITH CONDULETS -- NOT CHASE NIPPLE. 6. PLEASE PROVIDE ARC FLASH WARNING LABELING FOR PANELS. |