Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03406
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/17/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
08/14/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* - CONTRACTOR'S SCOPE OF WORK IS COMPLETE - WE HAVE A DOUBLE DUPLEX OUTLET IN PATIENT CARE AREA THAT DOES NOT MEED THE REQUIRMENTS OF 517.13 |
|
08/11/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
08/05/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* ELECTRIC FOR CLOSET IS COMPLETE. NEW EQUIPMENT APPREARS TO EXCEED SCOPE OF THIS PERMIT. PLEASE PROVIDE INSPECTION HISTORY FOR WIRING IN AREA OF NEW EQUIPMENT TO VERIFY 517.13(A) & (B) |
|
08/02/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* SOUTHWEST HEART NUCLEAR DEPARTMENT 1. WE STILL HAVE BOX OVERFILL 2. PLEASE VERIFY EXISTING WIRING METHODS MEET REQUIREMENT OF 517.13 WE HAVE A PATIENT CARE AREA WITH NEW MEDICAL EQUIPMENT. 3. THIS PERMIT FOR A GENERAL OFFICE NOT MEDICAL |
|
07/31/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* LOCKED NO ACCESS |
|
07/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INTERMEDIATE NOT APPROVED TO CLOSE WALLS. 2. OPEN CEILING AND PLEASE PROVIDE A LADDER TO INSPECT |