Permit: T06CM03406

Parcel: 13316030E

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03406

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/14/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
- CONTRACTOR'S SCOPE OF WORK IS COMPLETE
- WE HAVE A DOUBLE DUPLEX OUTLET IN PATIENT CARE AREA THAT DOES NOT MEED THE REQUIRMENTS OF 517.13
08/11/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/05/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
ELECTRIC FOR CLOSET IS COMPLETE.
NEW EQUIPMENT APPREARS TO EXCEED SCOPE OF THIS PERMIT.
PLEASE PROVIDE INSPECTION HISTORY FOR WIRING IN AREA OF NEW EQUIPMENT TO VERIFY 517.13(A) & (B)
08/02/2006 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
SOUTHWEST HEART NUCLEAR DEPARTMENT
1. WE STILL HAVE BOX OVERFILL
2. PLEASE VERIFY EXISTING WIRING METHODS MEET REQUIREMENT OF 517.13 WE HAVE A PATIENT CARE AREA WITH NEW MEDICAL EQUIPMENT.
3. THIS PERMIT FOR A GENERAL OFFICE NOT MEDICAL
07/31/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
LOCKED NO ACCESS
07/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INTERMEDIATE NOT APPROVED TO CLOSE WALLS.
2. OPEN CEILING AND PLEASE PROVIDE A LADDER TO INSPECT