Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/05/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 08/02/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
| 07/31/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 07/18/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SUPPORT M/C CABLE UP OFF OF GRID. SUPPORT AS PER 300.11 2. WE HAVE A BROKEN M/C ARMOR 3. WE HAVE BOX OVERFILL 4. SUPPORT VDV CABELING AS PER 725.6, 760.6, 800.6 |
|
| 07/12/2006 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |