Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T06CM03393


Addresses:

1100 S RANDOLPH WY


Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T06CM03393

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/22/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
APPROVED PER REVISED CITY APPROVED PLAN ON SITE
(2) BACKFLOW CERTIFICATIONS TURNED IN
(1) BACTERIA REPORT TURNED IN
03/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
03/15/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
CONTRACTOR CANCELLED
02/23/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
MET WITH HOWARD DUTT PARK & REC,
SCOTT BARTON REID PARK ZOO
MARK, CIMROCK
SHALL SEPARATE & PROVIDE BACKFLOW PROTECTION FOR OTTER MAKE UP POTABLE WATER SUPPLY & THIS PROJECT. SHALL REVISE & HAVE CITY APPROVAL OF POTABLE WATER CONNECTION TO EXISTING, SHALL PROVIDE BACKFLOW CERTIFICATIONS, SHALL HAVE OK FOR PLASTIC BODY INSTEAD OF BRASS BODY FOR CONTROL VALVES. SHALL PROVIDE REVISION & CITY APPROVAL OF 4" SANITARY DRAINAGE TO GRAY WATER SYSTEM WITH TERMINATIONS. SHALL HAVE ELECTRICAL INSPECTION WITH APPROVAL FOR FINAL. SHALL PROVIDE CHLORINIZATION & HAVE BACTERIA REPORT FOR FINAL FOR POTABLE WATER AT THIS EXHIBIT.
02/21/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
HAVE ELECTRICAL INSPECTION ADDED TO YOUR PERMIT AND HAVE ELECTRICAL APPROVAL FOR FINAL

1. SHALL HAVE CORRECT CONNECTON AND PROTECTION OF POTABLE WATER SYSTEM FOR WATER FEATURES.
NOTE: THE CONNECTION FOR WATER FILL AT OTHER FILTER PUMPS HAS EXTREME POTENTIAL FOR CROSS CONTAMINATION AND SHALL BE ADDRESSED IMMEDIATELY.
2. PRESSURE REGULATORS ON WATER SUPPLIES REQUIRE PRESSURE RELIEFS DOWN STREAM.
3. PROVIDE APPROVED PLAN OF CONTINUATION OF 4" DRAINAGE PIPING TO COMPLETE YOUR GRAY WATER SYSTEM.
4. PROVIDE CONTROL VALVES PER PLAN AND HAVE ZOO PROVIDE INFORMATION ON REGULATORS REQUIRED.