Permit: T06CM03370

Parcel: 129040990


Addresses:

1916 E 9TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/28/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
CONTRACTOR TO BOND CENTER MODULE/ARRAY
08/22/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. GROUNDING CONNECTIONS TO PANELS ARE STILL LOOSE IF SCREWS ARE STRIPPED THEY WILL NEED TO BE RE-TAPPED OR USE LUG WITH NUT AND BOLT. ALSO, WRAP EQUIPMENT GROUND 2/3RDS AROUND SCREW THEN PINCH AND TIGHTEN CONDUCTOR - DO NOT OVERLAP EQUIPMENT GROUND AROUND GROUND SCREW.

WILL NEED TO PAY REINSPECTION FEE BEFORE FINAL APPROVAL.
08/16/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
EQUIP. GROUNDING CONNECTIONS AT PANELS ON
ROOF ARE LOOSE.