Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T06CM03356
Inspection Description - FIRE - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/11/2008 | FIRE - FINAL | Approved | ||
| 01/04/2008 | FIRE - FINAL | Not ready for Inspection | Correct sprinkler coverage in the following areas: 1.Northeast corner show room floor by door head 8' 6" from wall 2.Office storage room heads 9' off wall (x2) only 7' 6" allowed 3.Soffit above sale counter heads over 8' need to install heads in soffit. 4.Sales floor (southeast) at the start of the ceiling change from 14' to 8', heads 8' from change need to cover dead spot area. Need to install FD key system on all gates. |