Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03356
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/14/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 01/11/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. SEVERAL OUTDOOR WALL PACKS NOT OPERATING 2. FINISH WORKING ON EM LIGHTS 3. NEED SPECIAL INSPECTION REPORT FOR OUTDOOR LIGHTING 4. EVERYTHING ELSE OK |
|
| 01/10/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK FINAL BUILDING B & C 2. OK FINAL FOR ROOF |
|
| 01/09/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* NOT ALL EM LIGHT WORKING |
|
| 01/08/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* BUILDING B STORAGE 1. INSTALL 2 GROUND RODS AND CONNECT TO NEUTRAL BAR OF SERVICE DISCONNECT & BOND TO BUILDING STEEL 2. BLANK OPEN KNOCKOUTS 3. NEED TO CHECK OUTSIDE LIGHTS 4. SUPPORT JUNCTION BOXES ABOVE PANEL 5. CONNECT GROUND WIRE TO JUNCTION BOXES BLDG C 1. INSTALL NEUTRAL BAR IN DISCONNECT |
|
| 01/07/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* ROOF INSPECTION 1. INDICATE ACCESSORIES INSTALLED IN UNITS 2. INSTALL BONDING BUSHINGS AROUND CONCENTRIC KNOCKOUTS 3. INSTALL K.O SEAL IN EXHAUST FAN #1 4. CANNOT USE TECH SCREWS FOR GROUNDING 5. GROUND SET TV DISHES |