Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/11/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* 1. OK TO COVER ALL AREAS 2. CORRECTIONS MADE OK |
|
| 07/27/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. OK TO COVER WALLS 2. CLOSET FLANGES ARE NOT SECURED TO THE FLOOR |
|
| 07/26/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* SEE 15400 PLUMBING INSULATION SECURE CLOSET FLANGES TO FLOOR |
|
| 07/25/2006 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. NO TEST ON ABS 2. SUPPORT ALL VERTICAL AND ALL OVERHEAD PIPING 3. COPPER NOT INSTALLED PER PLAN NO PROVISION MADE FOR WATER HEATER COLD WATER TIED INTO HOT WATER 4. NEED TO SEE CLOSET FLANGES. |