Permit: T06CM03339

Parcel: 126070030


Addresses:

522 N ALVERNON WY


Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Permit Number - T06CM03339

Inspection Description - PLUMBING - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/17/2006 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
08/15/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
INSTALL HANGERS ON OVERHEAD HORIZONTAL PIPING
PROVIDE INSULATION THAT MEETS SPECS AND INSTALL CORRECTLY.
CLOSET FLANGES OK
PIPE SIZING OK
DWV OK
08/11/2006 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
PLAN SPECS 1" CW SUPPLY
ALSO REMOVE EXCESS FLUX FROM SOLDER JOINTS
OK TO INSULATE HW PER PLAN AFTER REMOVING FLUX
SUPPORT 3" VENT AT ROOF PENETRATION
MAKE PIPING PLUMB LEVEL AND SQUARE
PLAN REVISION FOR WH
SECURE CLOSET FLANGES TO FLOOR AS REQUIRED BY UPC INSTALLATION STANDARDS
08/03/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
PROVIDE TEST ON PIPING
08/02/2006 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*