Permit: T06CM03339

Parcel: 126070030


Addresses:

522 N ALVERNON WY


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM03339

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/17/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
10/10/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) VERIFY TYPE OF FUSES NEEDED AT SERVICE
09/18/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. SUPPORT M/C CABLES WITHIN 12" OF BOXES & USE LISTED AND APPROVED STRAPS.
2. TIGHTEN LOOSE SET SCREW FITTINGS.
3. REMOVE NEUTRAL BOND AT SUB-PANEL
4. INSTALL REJECTION PINS & FUSES
5. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING
6. PROPERLY INSTALL HUB PLATE -
USE LISTED BY MANUFACTURER
7. A BOND IS NEEDED FOR TEMP POWER
08/17/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO WIRING IN BATHROOM CEILINGS
08/11/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH WALLS EXCEPT PANEL LOCATION UNLESS APPROVED CITY OF TUCSON REVISION (BATH CEILINGS NOT READY)
08/02/2006 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROTECT MC CABLE AT SHALLOW JOIST
2. PROVIDE BACK BRACING TO SUPPORT BOXES WITH MC CABLE
3. FILL USUSED OPENING IN BOXES
4. WHERE ARE EXHAUST FANS
5. PLEASE VERIFY BOX FILL FOR CUT IN BOXES
6. WHERE IS NEW PANEL