Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM03339
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/17/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
10/10/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) VERIFY TYPE OF FUSES NEEDED AT SERVICE |
|
09/18/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. SUPPORT M/C CABLES WITHIN 12" OF BOXES & USE LISTED AND APPROVED STRAPS. 2. TIGHTEN LOOSE SET SCREW FITTINGS. 3. REMOVE NEUTRAL BOND AT SUB-PANEL 4. INSTALL REJECTION PINS & FUSES 5. SHEET METAL SCREWS NOT ALLOWED FOR GROUNDING 6. PROPERLY INSTALL HUB PLATE - USE LISTED BY MANUFACTURER 7. A BOND IS NEEDED FOR TEMP POWER |
|
08/17/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NO WIRING IN BATHROOM CEILINGS |
|
08/11/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH WALLS EXCEPT PANEL LOCATION UNLESS APPROVED CITY OF TUCSON REVISION (BATH CEILINGS NOT READY) |
|
08/02/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PROTECT MC CABLE AT SHALLOW JOIST 2. PROVIDE BACK BRACING TO SUPPORT BOXES WITH MC CABLE 3. FILL USUSED OPENING IN BOXES 4. WHERE ARE EXHAUST FANS 5. PLEASE VERIFY BOX FILL FOR CUT IN BOXES 6. WHERE IS NEW PANEL |