Permit: T06CM03338

Parcel: 108240840


Addresses:

2492 E RIVER RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
02/12/2007 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
02/08/2007 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
1) TEST AND EXPOSE ROOF DRAINS FOR INSPECTION
2) INSTALL EXPANSION JOINTS AT PLASTIC DRAINS
3) PROVIDE ACCESS TO ROOF
10/13/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
PIPE WRAPS OK FOR CONCRETE
09/08/2006 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
- OK TO COVER ROUGH PLUMBING
- RECALL ROUGH INSPECTION PRIOR TO CONCRETE FOR PIPE WRAP INSPECTION AND FS INSTALLATION.
- FIXTURE FITTINGS INSTALLED PER RED LINES ON SHELL PLAN.
- BUILDING SEWER CONNECTED TO PVC STUB AT 2 WAY CO
- CALL FOR ROUGH PLUMBING AND HCS WHEN APPROVED TI PLAN BECOMES AVAILABLE.
09/07/2006 PLUMBING - ROUGH, SOIL Not ready for Inspection IVRS - Inspection :*
- WATER TEST NOT TO TOP OF RISER
- GROUND WET FROM RAIN, UNABLE TO BE SURE THAT NO LEAKS EXIST.
- ALSO MUD HAS COVERED MOST OF THE PIPING, UNABLE TO CHECK FALL.
- SUPPORT WC TRAP ARM
- SHELL PLANS DO NOT SHOW FIXTURES TO BE INSTALLED, REDLINE PLANS.