Permit: T06CM03331

Parcel: 103110480

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/26/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
12/07/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
PORCHES NOT READY
MAIN ADDITION OK
08/11/2006 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SUBMIT AS BUILT DRAWINGS FOR APPROVAL RE: RELOCATION OF NEW SUB PANEL, RELOCATION OF UNDERGROUND CONDUIT, SIZE OF CONDUIT AND CONDUCTORS AND UPGRADE TO 20 AMP MAIN PANEL
2) INSTALL ADDITIONAL GROUND ROD FOR NEW SERVICE