Permit: T06CM03316

Parcel: 11615014A


Addresses:

219 N SILVERBELL RD

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/23/2007 BUILDING - FINAL Approved IVRS - Inspection :*
08/14/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) MISSING DEDICATED CIRCUIT FOR FRIDGE
2) NEED TO FIX GFI CIRCUIT AT KITCHEN
3) NEED TO FIX STEP AT MASTER BATH
4) MISSING GRILL AT MECHANICAL RETURN
5) NEED TO CHANGE ROOF CAP ON VTR
6) 1/2 HOT OPEN NEUTRAL AT MASTER BEDROOM
7) GAS LINE IN LAUNDRY NEEDS TO BE CAPPED
8) RELOCATE DISCONNECT BOX IN MECHANICAL ROOM
07/16/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED TO GET TEMP POWER APPROVED BEFORE FINALS