Permit: T06CM03283

Parcel: 141320060


Addresses:

10385 E YEW PL


Inspection Status: Approved

Inspection History: FRAMING

Permit Number - T06CM03283

Inspection Description - FRAMING

Inspection Status - Approved

Date Description Inspector Results Comments
11/07/2006 FRAMING Approved IVRS - Inspection :*
11/02/2006 FRAMING Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspection
Improper ground splice on ufer-repeat
No address on electric panel
Garage shearwall #1 requires pins at 18" on center
Access to furnace blocke by ductwork
Provide 30" clearance under duct-repeat
4 gang electric box must be supported two ends-repeat
Refee
10/31/2006 FRAMING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) COMPLETE ITEMS 1, 2 & 5
2) SHOVING A GROUND WIRE INTO FOAM AND STAPLING IS NEXT TO A CUT UFER IS NOT AN ACCEPTABLE UFER REPAIR
3) BRING GREEN TRACER WIRE TO SURFACE AT CLEANOUT
4) PLEASE COMPLETE ALL ITEMS PRIOR TO RECALLING INSPECTIONS
10/16/2006 FRAMING Partial Approval IVRS - Inspection :*
1) TIGHTEN RED HEADS
2) ACCESS TO FURNACE BLOCKED BY DUCTWORK
3) COPPER UFER AND GAS BOND MISSING
4) WIRES CUT DINING AREA
5) SUPPORT FOUR GANG BOX L/R AT HALL
6) MAIN COPPER SERVICE MISSING
7) NO SUPPLY OR DWV WATER TESTS
8) TUB AND SHOWER COPPER MISSING
9) FLEX ON HALL EXHAUST FAN DAMAGED AND LAUNDRY