Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM03283
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/07/2006 | FRAMING | Approved | IVRS - Inspection :* | |
11/02/2006 | FRAMING | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspection Improper ground splice on ufer-repeat No address on electric panel Garage shearwall #1 requires pins at 18" on center Access to furnace blocke by ductwork Provide 30" clearance under duct-repeat 4 gang electric box must be supported two ends-repeat Refee |
|
10/31/2006 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) COMPLETE ITEMS 1, 2 & 5 2) SHOVING A GROUND WIRE INTO FOAM AND STAPLING IS NEXT TO A CUT UFER IS NOT AN ACCEPTABLE UFER REPAIR 3) BRING GREEN TRACER WIRE TO SURFACE AT CLEANOUT 4) PLEASE COMPLETE ALL ITEMS PRIOR TO RECALLING INSPECTIONS |
|
10/16/2006 | FRAMING | Partial Approval | IVRS - Inspection :* 1) TIGHTEN RED HEADS 2) ACCESS TO FURNACE BLOCKED BY DUCTWORK 3) COPPER UFER AND GAS BOND MISSING 4) WIRES CUT DINING AREA 5) SUPPORT FOUR GANG BOX L/R AT HALL 6) MAIN COPPER SERVICE MISSING 7) NO SUPPLY OR DWV WATER TESTS 8) TUB AND SHOWER COPPER MISSING 9) FLEX ON HALL EXHAUST FAN DAMAGED AND LAUNDRY |