Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T06CM03275
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 8 IN HOUSE BACKFLOW CERTIFICATIONS TURNED IN 10 PSI TEST ON GAS SYSTEM THAT WAS ON AT METER FOR COOKING BATTERY ONLY PER APPROVED CITY PLAN OK |
|
07/31/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. HAVE ALL DISPENSING APPLIANCES INSTALLED CORRECTLY TO BE ABLE TO IDENTIFY NEED FOR CORRECT BACKFLOW PROTECTION. 2. PROVIDE CORRECT BACKFLOW PROTECTION FOR ICE MACHINE 3. PROVIDE RIGID FULL SIZE DRAIN SECURED CORRECTLY FOR FILTER SYSTEM AT ICE MACHINE 4. PROVIDE SIGNAGE FOR ANSUL VALVE LOCATION. 5. ALL INDIRECT DRAINS APPEAR TO BE NEW PROVIDE DIRECT P-TRAP IF OVER 5', P-TRAP & VENT IF OVER 15' 6. PROVIDE CITY APPROVED GAS ISOMETRIC OF YOUR GAS SYSTEM. NEW PIPING AT COOKING BATTERY WITH NEW APPLIANCES AND TESTING SHALL BE REQUIRED. 7. ALL INDIRECT DRAINS FOR SEPARATE APPLIANCES NEED TO BE SEPARATE AND SECURED CORRECTLY. 8. PROVIDE CERTIFICATIONS FOR BACKFLOW DEVICES. 9. CAP OLD CLOSET FLANGE AT WALK-IN COOLER |