Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T06CM03273
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/19/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
07/14/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SPRINKLER PIPING NOT APPROVED FOR SUPPORT OF VDV CABLEING. 2. OLD VDV CABLEING TO BE AS PER 725.3 & 800.3 NEW VDV CABLEING TO BE SUPPORTED AS PER 725.6 & 800.6 & 760.6 6' INTERVALS NOT OFF OF CONDUITS - TAPE NOT APPROVED FOR SUPPORT. 3. PLEASE VERIFY BOX FILL 314.16 4. SUPPORT M/C CABLES AS PER 300.11 5. PLEASE RE-SUPPORT EMT BACK TO STRUCTURE. OK 2X4 LAY INS *NOTE: BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 |