Permit: T06CM03273

Parcel: 12709011M

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
07/19/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/14/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SPRINKLER PIPING NOT APPROVED FOR SUPPORT OF VDV CABLEING.
2. OLD VDV CABLEING TO BE AS PER 725.3 & 800.3 NEW VDV CABLEING TO BE SUPPORTED AS PER 725.6 & 800.6 & 760.6
6' INTERVALS NOT OFF OF CONDUITS - TAPE NOT APPROVED FOR SUPPORT.
3. PLEASE VERIFY BOX FILL 314.16
4. SUPPORT M/C CABLES AS PER 300.11
5. PLEASE RE-SUPPORT EMT BACK TO STRUCTURE.
OK 2X4 LAY INS
*NOTE: BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20