Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03269
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/31/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
01/29/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* COMPLETE COMPRESSOR HOOKUP |
|
01/18/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* FINAL NOT READY - LIFTS AND COMPRESSORS TO BE INSTALLED FOR INSPECTION |
|
01/15/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY INSPECTION FOR ROOFTOP 1. PROVIDE DISCONNECTING MEANS FOR EXH. FANS - PER PLAN AND NEC 430.102 2. STRAP FLEX WITHIN 12" OF TERMINATIONS 3. WIRING TO AC TO BE INDIVIDUAL CONDUCTORS - NOT ROMEX AND ALL CORRECTLY IDENTIFIED COLORS. 4. ALL ROOFTOP EQUIPMENT TO BE IDENTIFIED WITH SOMETHING SUITABLE FOR ENVIRONMENT - NOT STICKER 5. PANEL DIRECTORIES TO BE IDENTIFIED PER NEC 408.4 AND TO DISTINGUISH BETWEEN CKT'S PARTIAL INTERIOR INSPECTION 1. LIFTS TO BE IN PLACE FOR INSPECTION SAME WITH OTHER EQUIPMENT 2. PROVIDE GFI PROTECTION FOR CORD CAP RECEPTACLES |