Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
Permit Number - T06CM03269
Inspection Description - ELECTRIC - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/18/2008 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
12/14/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK HARD LIDS BATHROOM SERVICE INSPECTION 1. NEED TO POST BOND FOR POWER 2. INSTALL FUSES 3. IDENTIFY SERVICE DISCONNECTS - NEC 230.72 B 4. REMOVE ALL PAINT UNDER LUGS - NEC 250.12 5. ARRANGE BONDING CONDUCTORS TO PREVENT OBJECTIONABLE CURRENT - NEC 250.6 6. BONDING CONDUCTORS UNDERSIZED - NEC 250.102 C 7. BOND METAL PIPING TO SERVICE - GAS/WATER/AIR - NEC 250.104 |
|
11/27/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1) OK FRAMED WALL COVER |
|
09/19/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : Work is not complete enough to inspect.| 950* 1) DO NOT CALL FOR INSPECTION BEFORE WORK IS COMPLETE OR A FEE WILL BE CHARGED |