Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2008 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
| 11/06/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK SERVICE TRENCH & GROUND RODS UFER TO BE BONDED TO G.E.C |
|
| 11/02/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* SECONDARY INSPECTION ONLY 1. GROUND RODS TO BE MINIMUM 6' APART 2. IF DRIVEN AT ANGLE, NO MORE THAN 45 DEG. 3. GROUND ELECTRODE FOR TELCO TO BE THE SAME USED FOR SERVICE - NOT SEPARATE GROUND ROD 4. A WARNING RIBBON IS TO BE INSTALLED MINIMUM 12" ABOVE SERVICE SECONDARY RACEWAYS OK TO BACKFILL UP TO GROUND RODS, DO NOT COVER RODS BEFORE APPROVAL 5. WHERE IS UFER? 6. NO APPROVAL OR INSPECTION FOR RACEWAYS IN WALLS |