Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/23/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 06/20/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. ELECT. CONTROL WIRING EXPOSED TO SUN ON ROOF. SEC 725.C NEEDS TO BE PROTECTED. 2. CONDENSATE DRAIN; OPEN TIE FOLLOWS TRAP, NOT AHEAD OF IT. CANNOT ESTABLISH PRESS. DIFFERENTIAL AS INSTALLED. CORRECT/RECALL |