Permit: T06CM03210

Parcel: 133243720

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T06CM03210

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
10/19/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
10/12/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. TIGHTEN LOOSE FITTINGS AND CORRECTLY WIRE WATER HEATER USE APPROVED GROUND.
2. EXIT LIGHTING AS PLANS TO BE ON CIRCUIT FOR AREA SERVED 700.12
3. CORRECTLY LABEL CIRCUITS
4. BREAKROOM GFCI NOT WIRED AS PLANS
5. INSTALL REJECTION PINS MAIN DISCONNECT
6. PROTECT SEALTITE FROM SHARP METAL EDGES
EXHAUST FAN
7. TIGHTEN LOOSE FITTINGS
8. BOND DISCONNECT ENCLOSURE
9. WE HAVE A GROUNDING CONDUCTOR CONNECTED TO AN UNGROUNEDED CIRCUIT BREAKER.
10. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO. 406.8