Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03210
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/19/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
10/12/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. TIGHTEN LOOSE FITTINGS AND CORRECTLY WIRE WATER HEATER USE APPROVED GROUND. 2. EXIT LIGHTING AS PLANS TO BE ON CIRCUIT FOR AREA SERVED 700.12 3. CORRECTLY LABEL CIRCUITS 4. BREAKROOM GFCI NOT WIRED AS PLANS 5. INSTALL REJECTION PINS MAIN DISCONNECT 6. PROTECT SEALTITE FROM SHARP METAL EDGES EXHAUST FAN 7. TIGHTEN LOOSE FITTINGS 8. BOND DISCONNECT ENCLOSURE 9. WE HAVE A GROUNDING CONDUCTOR CONNECTED TO AN UNGROUNEDED CIRCUIT BREAKER. 10. RECEPTACLE COVERS TO BE WEATHERPROOF WHETHER OR NOT PLUGGED INTO. 406.8 |