Inspection History: ELECTRIC - SERVICE RELOCATION

Permit Number - T06CM03210

Inspection Description - ELECTRIC - SERVICE RELOCATION

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2006 ELECTRIC - SERVICE RELOCATION Approved
09/22/2006 ELECTRIC - SERVICE RELOCATION Not ready for Inspection IVRS - Inspection :*
1. IF MANUFACTURERS FIXTURE CLIPS ARE USED THEY MUST BE EFFECTIVE.
2. SUPPORT M/C CABLE WITHIN 12" TO BOXES.
3. MISSING JUNCTION BOX COVER
4. WE HAVE BOX OVERFILL
5. SUPPORT WIRE NEEDED FOR RECESSED CANS.
6. SUPPORTS TO BE AS PER 300.11
7. VDV CABELING TO BE SUPPORTED NOT LAYING ON OTHER CONDUITS, DUCTS OR PIPES.
8. FINISH BREAKROOM
9. PLEASE ADD 02036 PERMIT