Permit: T06CM03210

Parcel: 133243720

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/01/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK WALLS & HARD LIDS
08/30/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. FILL UNUSED OPENING IN PANEL AND BOX
OK WALLS EXCEPT AS NOTED
08/28/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. SUPPORT & PROTECT VDV CABLEING 725.6
2. WE STILL HAVE A BROKEN M/C SHEATH
3. FINISH NORTH OF COLUMN IN CENTER

OK WALLS SOUTH OF CENTER COLUMN EXCEPT AS NOTED.
08/25/2006 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. WE HAVE BOX FILL PROBLEMS
2. SUPPORT MC WITHIN 12" OF BOXES
3. PROTECT MC IN CHANNEL OF STUDS
4. REPAIR BROKEN SHEATHING

OK EXTERIOR WALL
OK ONE SIDE.