Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM03205
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/20/2007 | FRAMING | Approved | IVRS - Inspection :* | |
03/13/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER SUPER |
|
03/02/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) CONCRETE SLAB WAS CUT TO MAKE CORRECTIONS TO A LEAK IN 3" ABS. IT IS OK TO INSULATE AND DRYWALL AT THIS TIME. I WILL APPROVE FRAMING WHEN FINAL POUR OF CEMENT AT CUT-OUT IS FINISHED. WAITING ON PAPERWORK |
|
02/02/2007 | FRAMING | Partial Approval | IVRS - Inspection :* | |
01/24/2007 | FRAMING | Cancelled | IVRS - RI canceled | |
01/18/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) REMOVE REBAR AT GARAGE 2) FIRESTOP AT CHASE OPENINGS 3) NEED NAILS IN JACK TRUSS HANGER 2ND FLOOR 4) SHIM ALL HEADERS EXT WALL 5) PEX LINE KITCHEN CEILING NEEDS TO BE ABOVE BLOCKING 6) PEX LINE IN DINING ROOM TO CLOSE TO CAN LIGHT 7) PSI GAS PRESSURE 8) BLOCK DUCT BOOT 3 SIDES DOWNSTAIRS BATH CORRECTED |
|
01/10/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* 1) CANCELLED PER SUPER-NOT READY |