Inspection History Details
Inspection Status: Approved
Inspection History: EXT METAL CLIPS/EXT SHEATHING
Permit Number - T06CM03205
Inspection Description - EXT METAL CLIPS/EXT SHEATHING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/02/2007 | EXT METAL CLIPS/EXT SHEATHING | Approved | ||
11/30/2006 | EXT METAL CLIPS/EXT SHEATHING | Partial Approval | IVRS - Inspection :* 1) NEED RETRO FOR MAS CLIP AT GARAGE N.W. CORNER |
|
11/16/2006 | EXT METAL CLIPS/EXT SHEATHING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) NORTH OPENING TO GARAGE MISSING A SIMPSON MAS CLIP 2) NEED STRAP AT EXT. SOUTH WALL BOTTOM PLATE, WHERE NOTCHED FOR PLUMBING 3) ADD STUD TO BOTTOM WALL, SO DBL STUDS ARE UNDERNEATH DBL GIRDER 4) ADD ONE MORE COIL STRAP TO PATIO GLU-LAM EACH SIDE 5) SHEARWALL REAR OF HOUSE, NAILING 4" ON CENTER 6) ADD RSP4 CLIP TO TRIPPLE STUDS NORTH WALL 1ST FLOOR 7) NAIL WIND BRACE TO EVERY STUD N.W. CORNER 8) NEED JOIST HANGERS FRONT OF GARAGE 9) SHEARWALL KITCHEN NEEDS MORE NAILS 4" ON CENTER 10) H2.5 DBL STUDS AT DBL GIRDER 2ND FLOOR 11) NO ACCESS TO ROOF |