Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM03200
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/08/2007 | FRAMING | Approved | IVRS - Inspection :* | |
02/07/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) ALL ITEMS HAVE BEEN CORRECTED 2) SINCE ALL ELECTRICAL WIRING WAS CUT OUT AND NEEDS TO BE REPLACED-I WILL NEED TO REINSPECT TO SIGN OFF ON FINAL FRAME |
|
02/02/2007 | FRAMING | Cancelled | IVRS - RI canceled | |
01/19/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEM #3 2) ITEM #4 SHEARWALL AT DEN NOT CORRECTED |
|
01/18/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ITEMS 1, 3, 4 AND 6 NEED TO BE CORRECTED |
|
01/09/2007 | FRAMING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) DBL STUD AT DBL GIRDER IN GARAGE NEEDS TO BE UNDERNEATH DBL GIRDER 2) NO INSULATION BEHIND TUB ENCLOSURE EXT. WALL AND MASTER BATH ALSO 3) SHOWER TUB BACKING MASTER BEDROOM 4) SHEAR TRANSFER NAILING ON 2 X 12 NOT PER 5/D3 5) MISSING RISER TO PANEL BOX 6) UFER CABLE LOOSE ON CLAMP 7) PLUG LEAKING AT OUTSIDE HOUSE BIB 8) ANTI-SIPHON MISSING 9) STAPLE IN OUTSIDE WATER LINE (PEX) |