Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
Permit Number - T06CM03198
Inspection Description - MECHANICAL - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/04/2006 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* OK FOR CEILING TILES FIRE WRAP OK PROVIDE A COPY OF CERTIFIED AIR BALANCE REPORT |
|
10/02/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* VAV 4 MISSING SUPPLY DUCT. INSULATE SUPPLY DUCTS FROM VAV 2 STRAP FLEX DUCT VAV1. FIRE WRAP OK. OK TO ENCLOSE DUCT SHAFT. PROVIDE CLIPS AT REDUCER. ACCESS DOOR NOT INSULATED CORRECTLY. |
|
09/28/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CHECKED WELDS ON GREASE DUCT. OK TO FIRE WRAP. PROVIDE LISTING ON FLEX CONNECTOR. |
|
08/24/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO CLOSE 1ST FLOOR SHAFT. STILL NEED TO COMPLETE FIRE DAMPERS. OK TO SHEETROCK 2 RESTROOMS & ROOM 109 UTILITIES. |
|
08/21/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* MED. PRESS SPIRAL PIPE, TOP BASEMENT INTS CHASE 10" & 12" OK TO WRAP. |
|
08/11/2006 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* |