Permit: T06CM03198

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T06CM03198

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
10/04/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
OK FOR CEILING TILES
FIRE WRAP OK
PROVIDE A COPY OF CERTIFIED AIR BALANCE REPORT
10/02/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
VAV 4 MISSING SUPPLY DUCT. INSULATE SUPPLY DUCTS FROM VAV 2 STRAP FLEX DUCT VAV1. FIRE WRAP OK.
OK TO ENCLOSE DUCT SHAFT. PROVIDE CLIPS AT REDUCER.
ACCESS DOOR NOT INSULATED CORRECTLY.
09/28/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CHECKED WELDS ON GREASE DUCT.
OK TO FIRE WRAP.
PROVIDE LISTING ON FLEX CONNECTOR.
08/24/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO CLOSE 1ST FLOOR SHAFT. STILL NEED TO COMPLETE FIRE DAMPERS. OK TO SHEETROCK 2 RESTROOMS & ROOM 109 UTILITIES.
08/21/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
MED. PRESS SPIRAL PIPE, TOP BASEMENT INTS CHASE 10" & 12" OK TO WRAP.
08/11/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*