Permit: T06CM03198

Parcel: 133170630


Addresses:

350 N WILMOT RD

Inspection Status: Approved

Inspection History: PLUMBING - MEDICAL GAS/TEST

Date Description Inspector Results Comments
09/14/2006 PLUMBING - MEDICAL GAS/TEST Approved IVRS - Inspection :*
- ALL PIPING INSTALLED AND UNDER 150 PSI TEST
- LABELS OK
- CALL FOR FINAL AFTER RECEIVING FINAL APPROVAL FROM CACTUS MEDICAL.
09/13/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
2 INSTALLERS WORKING
LINES STUBBED INTO RM FOR TIE IN
LABELS BEING INSTALLED
09/12/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval BELOW FLOOR ISOLATION VALVES BEING INSTALLED BE SURE TO SUPPORT BEFORE BRAZING TO ENSURE COMPLETE MAKE UP OF FITTINGS.
09/11/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval MED GAS PIPING CONTINUATION IN LOWER LEVEL
LOG BOOK OK
2 INSTALLERS WORKING
09/01/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
GROUND FLOOR OK TO COVER
08/31/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
08/30/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
150 PSI TEST ON ENTIRE SYSTEM DOWN STREAM OF ZONE VALVES. MA, MV, 02
08/29/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
TWO INSTALLERS WORKING
BLOW DOWN PERFORMED, ALL OUTLET BOXES TIED INTO
PAPERWORK UP TO DATE
08/28/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
MED GAS PROGRESS CONTINUING 2 INSTALLERS WORKING.
08/24/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
PAPERWORK CHECKED
2 INSTALLERS ON OVERHEAD PIPING
08/23/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
WESTEND OUTLET BOXES TIED IN
PROGRESS ON OVERHEAD PIPING
ULTRA HIGH PURITY NITROGEN BEING USED ON ALL 3 SYSTEMS.
08/22/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
PROGRESS CONTINUING. BLOW DOWN ON WEST END
INSTALLING OUTLET BOXES
ALARM PANEL MOUNTED.
08/21/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
08/18/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
08/17/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
DAILY LOG CHECKED
PIPING MOSTLY COMPLETE IN WEST END PATIENT ROOMS.
08/16/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
DAILY LOG BEING KEPT ON NOTE PAD, CONTRACTOR WILL OBTAIN PROPER FORMS FROM CACTUS MEDICAL
OUTLET BOXES BEING INSTALLED, OVERHEAD O(2) AND MA W/PARTIAL TEST ON PIPING INSTALLED.
CALL FOR DAILY INSPECTIONS.
08/14/2006 PLUMBING - MEDICAL GAS/TEST Not ready for Inspection NO PAPERWORK ON SITE
CALL FOR MASONRY INSPECTION
08/10/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
2" MV, 1" MA AND 1" 02 VALVE BOX INSTALLED & PIPED, PIPING OVERHEAD IN PROGRESS. HAVE PAPERWORK ON SITE. ISOLATION STUDS AND SAFETY PLATES NOT YET IN PLACE.
08/08/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
CAPPED PIPING ON RACK, TYPE K COPPER
BRAZING HAS NOT STARTED
DO CALL IN FOR DAILY INSPECTIONS IF PROGRESS IS BEING MADE.
08/07/2006 PLUMBING - MEDICAL GAS/TEST Partial Approval IVRS - Inspection :*
JIM SAMULSON 940-2056
HANGERS INSTALLED
MATERIAL STORAGE IN GANG BOX
CAPPED PIPING ON SITE. PROTECTED FROM DAMAGE
UHP NITROGEN, ALARMED REGULATOR AND OXYGEN SENSOR ON SITE.