Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
Permit Number - T06CM03198
Inspection Description - PLUMBING - INTERMEDIATE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/22/2006 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
09/12/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* INSTALL PERM CAP AT DEMOED SINK ABOVE CEILING IN CAFETERIA |
|
08/31/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - ALL DOMESTIC PIPING AND SANITARY PIPING GROUND FLOOR IS OK TO COVER. - NEED GAS UNDER TEST LABELING IN PROGRESS - ISOLATION AND SAFETY PLATES NEEDED. |
|
08/28/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CW, HW AND HWR W/100 PSI TEST OK TO INSULATE. DWV OK PROVIDE PERM CAP ON C1 |
|
08/21/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* - WATER TEST AT P-2A OK - PROVIDE PIPE WRAP PROTECTION ON ALL PIPING PENETRATING CONCRETE. - PROVIDE PERMANENT CAPS AT TEST TEES AND P-5 - MED GAS PROGRESS OK LOG BOOK ON SITE. |
|
08/18/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* DWV PIPING W/TEST OK EXCEPT FOR T.R 112.113 WATER NOT UNDER TEST ROOF DRAIN OFFSET W/TEST OK MED GAS PROGRESS OK LOG BOOK OK |
|
08/10/2006 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* |