Permit: T06CM03197

Parcel: 103090800

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/27/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/11/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL SERVICE CONDUCTORS
2. BOND SERVICE RACEWAYS
3. INSTALL ADDRESS ON SERVICE
4. IDENTIFY SERVICE DISCONNECT
5. IDENTIFY NEUTRAL
6. INSTALL FUSES
7. TIGHTEN/TORQUE ALL CONNECTIONS & FITTINGS
8. BOND BUILDING STEEL & SPRINKLER PIPE & BOND TO SERVICE.
9. NEED EQUIPMENT GROUND TO PANEL
10. TRANSFORMER TO HAVE PROPER BACK CLEARANCE
11. BOND SEAL TITE - PANEL TO TRANSFORMER