Permit: T06CM03193

Parcel: 11005098A


Addresses:

4627 E GLENN ST

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
04/23/2007 BUILDING - FINAL Approved IVRS - Inspection :*
04/20/2007 BUILDING - FINAL Partial Approval IVRS - Inspection :*
1) NO POWER CIRCUIT 20 BATH GFCI
04/19/2007 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
CANCELLED BY ROSE
04/17/2007 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) POST ADDRESS VISIBLE FROM STREET
2) SECURE LIQUID TIGHT 12" FROM DISCONNECT BOX CONDENSATE
3) PAINT 90 FITTING CONDENSATE
4) ANTI-TILT STOVE
5) GFCI PROTECT MASTER BATH OUTLET
6) LABEL MAIN SERVICE PLUMBING TYPE