Permit: T06CM03187

Parcel: 11520001N

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T06CM03187

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
10/13/2006 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
09/14/2006 ELECTRIC - INTERMEDIATE Denied 1. SECONDARY SERVICE RACEWAYS BONDING CONDUCTOR IS UNDERSIZED -- NEC 250.102.C
2. GROUNDING ELECTRODE SYSTEM TO INCLUDE UFER IF AVAILABLE -- NEC 250.50
3. BONDING CONDUCTOR FROM TERM CAN TO GUTTER UNDERSIZED - NEC 250.102.C (BOTH NIPPLES)
4. GUTTER NEEDS TO BE BONDED -- NEC 250.92
5. CONDUCTORS NEED TO BE ARRANGED TO PREVENT OBJECTIONABLE CURRENT -- NEC 250.6
6. BOND TO TERM CAN UNDERSIZED -- NEC 250.102.C
7. BOND FOR TERM CAN TO CT CAN UNDERSIZED -
NEC 250.102.C
8. GROUNDING ELECTRODE CONDUCTOR NEEDS TO CONNECT DIRECTLY TO SERVICE NEUTRAL OR THROUGH AN APPROVED MAIN BONDING JUMPER -- NEC 250.24
9. PROVIDE PROTECTION FOR SERVICE -- NEC 110.27 B