Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 09/14/2006 | ELECTRIC - INTERMEDIATE | Denied | 1. SECONDARY SERVICE RACEWAYS BONDING CONDUCTOR IS UNDERSIZED -- NEC 250.102.C 2. GROUNDING ELECTRODE SYSTEM TO INCLUDE UFER IF AVAILABLE -- NEC 250.50 3. BONDING CONDUCTOR FROM TERM CAN TO GUTTER UNDERSIZED - NEC 250.102.C (BOTH NIPPLES) 4. GUTTER NEEDS TO BE BONDED -- NEC 250.92 5. CONDUCTORS NEED TO BE ARRANGED TO PREVENT OBJECTIONABLE CURRENT -- NEC 250.6 6. BOND TO TERM CAN UNDERSIZED -- NEC 250.102.C 7. BOND FOR TERM CAN TO CT CAN UNDERSIZED - NEC 250.102.C 8. GROUNDING ELECTRODE CONDUCTOR NEEDS TO CONNECT DIRECTLY TO SERVICE NEUTRAL OR THROUGH AN APPROVED MAIN BONDING JUMPER -- NEC 250.24 9. PROVIDE PROTECTION FOR SERVICE -- NEC 110.27 B |