Permit: T06CM03181

Parcel: 116124570


Addresses:

509 N CUESTA AV #01

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
02/23/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
02/21/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE CORRECTION #2 FROM PREVIOUS INSPECTION WILL PAY REINSPECTION FEE IF NOT CORRECT NEXT INSPECTION
02/16/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. CONNECT UFER TO BOTH - NEC 250.50
2. USE LISTED GUY KITOR STIFF ARMS FOR MAST SUPPORT AND INSTALL SO IT IS EFFECTIVE ALSO, SECURE INTO STRUCTURE -- NEC 230.28
02/14/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. EQUIPMENT GROUNDS IN BOXES NEED TO BE TWISTED AND THEN PROPERLY CRIMPED.
2. STILL NEED TO DO CORRECTIONS #3 & #7 FROM PREVIOUS INSPECTION
01/31/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE PROPER CRIMPING TOOL FOR CRIMP SLEEVES ON GROUNDS -- NEC 110.3 B
2. NEED NAIL PLATES IN SEVERAL LOCATIONS - NEC 300.4D
3. NEED RECEPTACLE WITHIN 6' OF BROKEN WALL LINES -
NEC 210.52
4. SUB-PANEL NOT ALLOWED IN CLOSET -
NEC 240.24D, NEC 110
5. CHIME TRANSFORMER NOT ALLOWED IN CLOSET -
CITY OF TUCSON
6. INSTALL SUB-PANELS AND FEEDERS, WIRE BATH FAN
7. NEED KITCHEN COUNTER RECEPTACLE WITHIN 24" OF SINK AND WITHIN 24" OF WALL FOR COUNTERTOPS - NEC 210.52C