Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/23/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 02/21/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* SEE CORRECTION #2 FROM PREVIOUS INSPECTION WILL PAY REINSPECTION FEE IF NOT CORRECT NEXT INSPECTION |
|
| 02/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. CONNECT UFER TO BOTH - NEC 250.50 2. USE LISTED GUY KITOR STIFF ARMS FOR MAST SUPPORT AND INSTALL SO IT IS EFFECTIVE ALSO, SECURE INTO STRUCTURE -- NEC 230.28 |
|
| 02/14/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EQUIPMENT GROUNDS IN BOXES NEED TO BE TWISTED AND THEN PROPERLY CRIMPED. 2. STILL NEED TO DO CORRECTIONS #3 & #7 FROM PREVIOUS INSPECTION |
|
| 01/31/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE PROPER CRIMPING TOOL FOR CRIMP SLEEVES ON GROUNDS -- NEC 110.3 B 2. NEED NAIL PLATES IN SEVERAL LOCATIONS - NEC 300.4D 3. NEED RECEPTACLE WITHIN 6' OF BROKEN WALL LINES - NEC 210.52 4. SUB-PANEL NOT ALLOWED IN CLOSET - NEC 240.24D, NEC 110 5. CHIME TRANSFORMER NOT ALLOWED IN CLOSET - CITY OF TUCSON 6. INSTALL SUB-PANELS AND FEEDERS, WIRE BATH FAN 7. NEED KITCHEN COUNTER RECEPTACLE WITHIN 24" OF SINK AND WITHIN 24" OF WALL FOR COUNTERTOPS - NEC 210.52C |