Permit: T06CM03177

Parcel: 10612017R

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/03/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
12/21/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
REFEE
THERE ARE 10 VENTS ON THIS BUILDING THAT ARE NOT PROTECTED FROM UV RAYS.
THIS IS THE 6TH FINAL INSPECTION
YOU ARE BEING ASSESSED A REFEE BECAUSE YOU HAVE NOT COMPLETED ALL OF THE REQUESTED CORRECTIONS. NO FINAL INSPECTIONS WILL BE PERFORMED UNTIL FEE IS PAID.
12/11/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. WEST TOILET ROOM C O HAS A PLASTIC PLUG WITH A HOLE DRILLED IN IT, THE COVER HAS FALLEN OFF. PROVIDE THE PROPER FITTING FOR THIS APPLICATION.
2. THE WH EXPANSION TANK IS UNDER STRAIN FROM PLUMBERS TAPE AND IS TOUCHING A COPPER WATER LINE.
PTAPE IS NOT AN APPROVED HANGER. SUPPORT EXPANSION TANK WITH AN APPROVED PIPE SUPPORT AND DO NOT STRAIN PIPING.
3. OVERHEAD HORIZONTAL COPPER UNDER 2" REQUIRES SUPPORT AT 6' MAX. INSTALL PIPE SUPPORTS ON 1/2" HORIZONTAL COPPER ABOVE CEILING.
4. UPC REQUIRES THAT EXPOSED PLASTIC VENT TERMINATIONS BE PROTECTED FROM UV RAYS W/LATEX PAINT. PREVIOUSLY LADDER ACCESS TO ROOF HAS NOT BEEN PROVIDED. IT WAS ASSUMED THAT YOUR VENT TERMINATIONS WERE PROTECTED AS REQUIRED. IT HAS COME TO MY ATTENTION THAT THEY WERE NOT. ALL PLASTIC VENTS ON THIS BUILDING WILL BE PROTECTED BEFORE I WILL FINAL ANY REMAINING PERMITS!
11/29/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PAINT ALL EXPOSED PLASTIC VENT PIPING ON ROOF
DO NOT DRILL OR TAP PLASTIC CO PLUGS ALSO MAKE PLUGS GAS TIGHT W/THE USE OF APPROVED THREAD SEALANT.
RESTROOMS ARE CONSIDERED PUBLIC USE
PROVIDE DIELECTRIC PROTECTION BETWEEN WH AND COPPER PIPING.
SUPPORT EXP. TANK
CORRECT ELECTRICAL CONNECTION HAVE ELECTRICAL INSPECTOR CHECK IT.
PROVIDE DRAIN ON PAN ABOVE CEILING.
11/21/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CLEAN OUT PLUGS
2. PROVIDE LADDER ACCESS FOR WH INSPECTION
3. PUBLIC USE LAVATORIES REQUIRE MIXING VALVE/TEMPERATURE LIMITING DEVICE OTHER THAN WH CONTROL.
11/08/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) CAP OPEN SEWER PIPING IN OCCUPIED BLDG
08/24/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
08/18/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*