Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2006 | ELECTRIC - FINAL | Approved | ||
| 12/11/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION ONLY 1. UNIT IS NOT CLEARLY IDENTIFIED AT SERVICE. 2. PLANS CALL FOR 200 AMP SUB-PANEL, YOU HAVE 125 AMP? 3. REDO PANEL SCHEDULE SO IT IS CLEAR AND LEGIBLE. 4. HAVE SEVERAL LOOSE RECEPTACLES THROUGHOUT, TIGHTEN AS NEEDED AND MAKE FLUSH TO WALL. 5. CEILING COVERED WITHOUT INSPECTION REMOVE TILES FOR INSPECTION. 6. MC TO BE SECURED WITHIN 12" OF TERMINATIONS. 7. HAVE OVERFILLED J-BOXES AND MAKE SURE ALL ARE GROUNDED. 8. IDENTIFY WHITE USED AS HOT AT ALL TERMINATIONS. 9. PROVIDE LADDER FOR ROOFTOP INSPECTION AND CEILING INSPECTION. |
|
| 11/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |