Inspection History Details
Inspection Status: Approved
Inspection History: FRAMING
Permit Number - T06CM03176
Inspection Description - FRAMING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2007 | FRAMING | Approved | IVRS - Inspection :* | |
10/11/2007 | FRAMING | Partial Approval | IVRS - Inspection :* 1) LEAK ON PLUMBING ABS UNDER BATH TUB 2) NEED SUPPORT ELECTRICAL J-BOX AT MECHANICAL ROOM 3) NEED TO PROTECT CONDUCTORS COMING FROM SERVICE PANEL THRU OSB 4) NEED TO SEAL (CAULK) AROUND ALL ELECTRIC CUT OUTS ON LATH 5) FIRE SEAL CHASE 2ND FLOOR 6) STRAP DUCT 2ND FLOOR |
|
09/17/2007 | FRAMING | Not ready for Inspection | IVRS - Inspection :* |