Permit: T06CM03173

Parcel: 11616301C

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/23/2009 ELECTRIC - FINAL Approved IVRS - Inspection :*
01/09/2009 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
*AREA OCCUPIED WITHOUT INSPECTIONS
1. REMOVE CEILING TILES FOR INSPECTIONS
2. FUEL DISPENSERS TO BE AS PER 514.11 & 514.13
3. OLD CABINET FROM PANEL TO HAVE SOLID COVER OF EQUAL THICKNESS OF ORIGINAL
4. DISCONNECTING MEANS AND BOXES TO BE FOR DAMP/WET LOCATION IN WALK-IN BOX
5. SEAL CONDUITS TO WALK IN BOX AS PER 300.7
6. EM BALLAST TO BE INSIDE OF FIXTURE
7. RECEPTACLE MOUNTING 406.4(C)
8. REMOVE DEVICES IN STUD WALLS UNTIL READY FOR FINAL