Permit: T06CM03173

Parcel: 11616301C

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
01/23/2009 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
01/22/2009 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. INSTALL BOX EXTENDERS FOR DEVICES BOXES
WHERE MORE THAN 1/4" EXPOSED AT P-RING TO
WALL SURFACE 314.20 NEC
2. OK OTHER ITEMS INSPECTION NOTES FOR 1/9/09 RECEIVED DISPENSER DISC. INFO.
01/09/2009 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
01/08/2009 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELED
11/07/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE PROPER METHODS AND APPROVED METHODS TO SUPPORT M/C
2. FINISH #1, 2, 3, 4 OF PREVIOUS INSPECTION
11/07/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CORRECTIONS NOTED THIS AM BY R.HOLLANDER HAVE BEEN MADE -- OK TO COVER SOFFITS

WILL NEED ACCESS PANEL AT EAST END OF SOFFIT
11/06/2008 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SUPPORT M/C CABLE WITHIN 12" OF CANS
2. GUTTER AND JUNCTION BOXES TO BE ACCESSIBLE
3. FILL UNUSED OPENINGS IN BOXES
4. TIGHTEN LOOSE FITTINGS
5. NUMBER OF CANS NOT AS PER PLANS
10/28/2008 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK NORTH WALL