Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/23/2009 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 01/22/2009 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. INSTALL BOX EXTENDERS FOR DEVICES BOXES WHERE MORE THAN 1/4" EXPOSED AT P-RING TO WALL SURFACE 314.20 NEC 2. OK OTHER ITEMS INSPECTION NOTES FOR 1/9/09 RECEIVED DISPENSER DISC. INFO. |
|
| 01/09/2009 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 01/08/2009 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELED |
|
| 11/07/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE PROPER METHODS AND APPROVED METHODS TO SUPPORT M/C 2. FINISH #1, 2, 3, 4 OF PREVIOUS INSPECTION |
|
| 11/07/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CORRECTIONS NOTED THIS AM BY R.HOLLANDER HAVE BEEN MADE -- OK TO COVER SOFFITS WILL NEED ACCESS PANEL AT EAST END OF SOFFIT |
|
| 11/06/2008 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SUPPORT M/C CABLE WITHIN 12" OF CANS 2. GUTTER AND JUNCTION BOXES TO BE ACCESSIBLE 3. FILL UNUSED OPENINGS IN BOXES 4. TIGHTEN LOOSE FITTINGS 5. NUMBER OF CANS NOT AS PER PLANS |
|
| 10/28/2008 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK NORTH WALL |