Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* OK FOR FINAL |
|
| 10/05/2007 | MECHANICAL - FINAL | Denied | RESCHEDULE WHEN OPEN FOR BUSINESS | |
| 06/22/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* MEZZANINE FLOOR & CEILING BELOW NOT FIRE RATED. DAMPERS NOT REQUIRED. EF-8 DID NOT BALANCE CORRECTLY. REPAIR AS NEEDED & REBALANCE. PROVIDE MAKE UP AIR TO EF-8 AS PER PLANS BLANK OFF EXTERIOR LOUVER. EVERYTHING ELSE IS OK |
|
| 05/31/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE A ROOF JACK AT CONDENSATE THRU ROOF. 2. MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY. 3. CONNECT WATER TO EVAP. COOLER & PROVIDE A ROOF JACK AT ELEC. PENETRATION. 4. FINISH CONNECTING DUCT SMOKE DETECTOR. 5. PROVIDE AN AIR BALANCE REPORT. 6. FINISH ALL MECHANICAL WORK 7. PROVIDE RUSKIN ACCESSORY SMOKE DETECTORS FOR SMOKE DAMPERS. |