Permit: T06CM03171

Parcel: 12218256C


Addresses:

3701 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/29/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
OK FOR FINAL
10/05/2007 MECHANICAL - FINAL Denied RESCHEDULE WHEN OPEN FOR BUSINESS
06/22/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
MEZZANINE FLOOR & CEILING BELOW NOT FIRE RATED.
DAMPERS NOT REQUIRED.
EF-8 DID NOT BALANCE CORRECTLY.
REPAIR AS NEEDED & REBALANCE.
PROVIDE MAKE UP AIR TO EF-8 AS PER PLANS
BLANK OFF EXTERIOR LOUVER.
EVERYTHING ELSE IS OK
05/31/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE A ROOF JACK AT CONDENSATE THRU ROOF.
2. MARK UNIT DATA PLATE W/PROPER HEAT STRIP INSTALLED AND FUSE ACCORDINGLY.
3. CONNECT WATER TO EVAP. COOLER & PROVIDE A ROOF JACK AT ELEC. PENETRATION.
4. FINISH CONNECTING DUCT SMOKE DETECTOR.
5. PROVIDE AN AIR BALANCE REPORT.
6. FINISH ALL MECHANICAL WORK
7. PROVIDE RUSKIN ACCESSORY SMOKE DETECTORS FOR SMOKE DAMPERS.