Permit: T06CM03171

Parcel: 12218256C


Addresses:

3701 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/20/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/08/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
* ROOF NOT LOOKED AT
* BATHROOMS OCCUPIED WITHOUT CLEARANCES

1. USE APPROVED EXTENDER RINGS IF BOX TO SURFACE IS MORE THAN 1/4" 314.20
2. LABEL PANELS AS PER 408.4 -- NO ABBREVIATIONS WHAT IS EXISTING SERVING
3. BOXES OVERFILLED - 314.16
4. FILL UNUSED OPENINGS IN BOXES - NOT EMPTY FITTINGS
5. SUPPORT CONDUIT FOR VENT FAN
6. MAINTAIN DEDICATED SPACE BELOW DISCONNECTS (COMPRESSOR) -- 110.26
7. USE REDUCING WASHERS WHERE HOLES DO NOT MATCH FITTINGS.
8. GROUNDING EQUIPMENT CONDUCTOR #6 & SMALLER TO BE GREEN ENTIRE LENGTH
9. LABEL DISCONNECT
10. ARE CONDUCTORS SIZED FOR ABOVE AMBIENT TEMPERATURES.
11. EMERGENCY LIGHTING TO BE ON CIRCUIT OF AREA
SERVED 700.12
12. MISSING EM & EXIT LIGHTING ROOM 110
04/18/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
04/18/2007 ELECTRIC - FINAL Partial Approval OK TO OCCUPY SLAES AREA ONLY DOES NOT INCLUDE BATHROOMS - LEAVE BARRIER TO THESE AREAS IN PLACE
04/06/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*