Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/08/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* * ROOF NOT LOOKED AT * BATHROOMS OCCUPIED WITHOUT CLEARANCES 1. USE APPROVED EXTENDER RINGS IF BOX TO SURFACE IS MORE THAN 1/4" 314.20 2. LABEL PANELS AS PER 408.4 -- NO ABBREVIATIONS WHAT IS EXISTING SERVING 3. BOXES OVERFILLED - 314.16 4. FILL UNUSED OPENINGS IN BOXES - NOT EMPTY FITTINGS 5. SUPPORT CONDUIT FOR VENT FAN 6. MAINTAIN DEDICATED SPACE BELOW DISCONNECTS (COMPRESSOR) -- 110.26 7. USE REDUCING WASHERS WHERE HOLES DO NOT MATCH FITTINGS. 8. GROUNDING EQUIPMENT CONDUCTOR #6 & SMALLER TO BE GREEN ENTIRE LENGTH 9. LABEL DISCONNECT 10. ARE CONDUCTORS SIZED FOR ABOVE AMBIENT TEMPERATURES. 11. EMERGENCY LIGHTING TO BE ON CIRCUIT OF AREA SERVED 700.12 12. MISSING EM & EXIT LIGHTING ROOM 110 |
|
| 04/18/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/18/2007 | ELECTRIC - FINAL | Partial Approval | OK TO OCCUPY SLAES AREA ONLY DOES NOT INCLUDE BATHROOMS - LEAVE BARRIER TO THESE AREAS IN PLACE | |
| 04/06/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |