Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2007 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 04/11/2007 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) SERVICE INSPECTION ONLY |
|
| 04/02/2007 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : The service is not per code.| 210* 1. BOND SERVICE RISERS - NEC 250.92, 250.102 2. NEED BUSHING #4 & LARGER CONDUCTOR - NEC 300.4F 3. BOND LUGS HAVE TO BIG CONDUCTOR UNDER THEM - NEC 110.3 B 4. INSTALL ADDRESS ON SERVICE METER BASE 5. IDENTIFY SERVICE DISCONNECTS - NEC 230.70 B 6. TIGHTEN ALL CONNECTIONS 7. BOND NEUTRAL TO SERVICE DISCONNECT ENCLOSURE - NEC 250.24 A5, 408.3 C 8. REMOVE, SEAL UNUSED RACEWAYS - NEC 110 9. INSTALL FEEDERS/FINISH FEEDER RACEWAYS 10. FEEDER PULL BOX UNDERSIZED - NEC 314.28 A2 |
|
| 03/06/2007 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* DISCUSSED SERVICE |