Permit: T06CM03171

Parcel: 12218256C


Addresses:

3701 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
06/20/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
04/06/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) VERIFY BOX FILL
2) PROPERLY SUPPORT FAN BOXES
3) ATTACH TO GRID FIXTURES AND 2 SUPPORT WIRE OPPOSITE CORNERS
4) MAKE UP DAMPER
5) APPROVED EXTENDER RINGS NEEDED AT DEVICES. FLOSH IF COMBSUTIBLE-1/4" BOX TO SURFACE NON COMBUSTIBLE 314.20
6) FINISH INTALLING DEVICES IN AREAS FOR TEMP OCCUPANCY
7) EM LIGHTING AND EXIT LIGHTING TO BE PER 700.12
8) SUPPORT CONDUITS PER CODE
9) SUPPORT WIRE NEEDED FOR EXIT LIGHTS
10) FILL UNUSED OPENINGS IN BOXES-NOT OLD FITTINGS
11) FINISH DEMO
12) PROPERLY SUPPORT VDV CABELING
13) PROVIDE FIXTURE INSTRUCTIONS
14) FINISH ELECTRIC WINDOW SHADES NOTE: 400.7 AND 8
03/28/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. SHEETROCK CEILINGS OFFICE AREA OK
2. RECALL FOR DROP CEILINGS WHEN READY