Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2007 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/06/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VERIFY BOX FILL 2) PROPERLY SUPPORT FAN BOXES 3) ATTACH TO GRID FIXTURES AND 2 SUPPORT WIRE OPPOSITE CORNERS 4) MAKE UP DAMPER 5) APPROVED EXTENDER RINGS NEEDED AT DEVICES. FLOSH IF COMBSUTIBLE-1/4" BOX TO SURFACE NON COMBUSTIBLE 314.20 6) FINISH INTALLING DEVICES IN AREAS FOR TEMP OCCUPANCY 7) EM LIGHTING AND EXIT LIGHTING TO BE PER 700.12 8) SUPPORT CONDUITS PER CODE 9) SUPPORT WIRE NEEDED FOR EXIT LIGHTS 10) FILL UNUSED OPENINGS IN BOXES-NOT OLD FITTINGS 11) FINISH DEMO 12) PROPERLY SUPPORT VDV CABELING 13) PROVIDE FIXTURE INSTRUCTIONS 14) FINISH ELECTRIC WINDOW SHADES NOTE: 400.7 AND 8 |
|
| 03/28/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. SHEETROCK CEILINGS OFFICE AREA OK 2. RECALL FOR DROP CEILINGS WHEN READY |